EK-DI-163AC10-A13 C
16.36 kW
Defrost: None
Product code: EK-DI-163AC10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 17,186 m³/h |
|---|---|
| External surface | 52.9 m² |
| Inner volume | 22.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 197 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | E |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EK-DI-163AC10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.88 | 6.64 | 6.49 | 6.40 | 6.30 | 6.20 | 6.11 | 6.08 | 6.42 | 6.91 | 6.71 | 6.64 | 6.54 | 6.39 |
| 5 | 8.18 | 7.98 | 7.85 | 8.62 | 8.50 | 8.37 | 8.24 | 8.18 | 8.63 | 9.28 | 8.99 | 8.89 | 8.73 | 8.50 |
| 6 | 10.25 | 10.09 | 9.97 | 11.02 | 10.90 | 10.76 | 10.60 | 10.51 | 11.09 | 11.92 | 11.52 | 11.37 | 11.17 | 10.85 |
| 7 | 12.26 | 12.20 | 12.18 | 13.53 | 13.45 | 13.31 | 13.14 | 13.03 | 13.75 | 14.79 | 14.28 | 14.09 | 13.82 | 13.41 |
| 8 | 14.21 | 14.29 | 14.38 | 16.08 | 16.06 | 15.97 | 15.81 | 15.70 | 16.57 | 17.83 | 17.23 | 17.00 | 16.67 | 16.15 |
| 9 | 17.87 | 18.14 | 18.34 | 18.58 | 18.67 | 18.64 | 18.53 | 18.44 | 19.48 | 20.99 | 20.31 | 20.05 | 19.66 | 19.04 |
| 10 | 19.67 | 20.12 | 20.57 | 21.00 | 21.28 | 21.35 | 21.30 | 21.25 | 22.47 | 24.24 | 23.50 | 23.21 | 22.78 | 22.06 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.14 | 5.93 | 5.80 | 5.73 | 5.66 | 5.59 | 5.52 | 5.50 | 5.82 | 6.27 | 6.10 | 6.04 | 5.96 | 5.83 |
| 5 | 7.27 | 7.07 | 6.95 | 7.64 | 7.55 | 7.45 | 7.35 | 7.31 | 7.72 | 8.31 | 8.07 | 7.98 | 7.86 | 7.67 |
| 6 | 9.05 | 8.88 | 8.78 | 9.69 | 9.60 | 9.49 | 9.36 | 9.30 | 9.82 | 10.56 | 10.23 | 10.11 | 9.94 | 9.68 |
| 7 | 10.87 | 10.74 | 10.69 | 11.84 | 11.77 | 11.66 | 11.51 | 11.44 | 12.08 | 13.00 | 12.58 | 12.42 | 12.20 | 11.85 |
| 8 | 12.62 | 12.59 | 12.60 | 14.05 | 14.02 | 13.92 | 13.78 | 13.70 | 14.47 | 15.58 | 15.06 | 14.87 | 14.60 | 14.16 |
| 9 | 15.91 | 16.01 | 16.13 | 16.27 | 16.30 | 16.24 | 16.12 | 16.04 | 16.93 | 18.25 | 17.67 | 17.44 | 17.11 | 16.57 |
| 10 | 17.71 | 17.97 | 18.19 | 18.44 | 18.56 | 18.57 | 18.48 | 18.41 | 19.47 | 21.00 | 20.36 | 20.10 | 19.72 | 19.11 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 23.504 | 20.360 |
| SC2 | 0 | 8 | 15.697 | 13.699 |
| SC3 | -18 | 7 | 13.504 | 11.816 |
| SC4 | -25 | 6 | 9.973 | 8.780 |
| SC5 | -34 | 6 | 10.224 | 9.025 |
| A | 1725 mm |
|---|---|
| B | 900 mm |
| C | 1150 mm |
| F | 860 mm |
| G | 1440 mm |
| E | 1335 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 1725 mm |
|---|---|
| Width | 1440 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.