EK-DI-163AE10-A13 C
22.84 kW
Defrost: None
Product code: EK-DI-163AE10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,413 m³/h |
|---|---|
| External surface | 79.4 m² |
| Inner volume | 33.1 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 225 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EK-DI-163AE10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.66 | 9.43 | 9.29 | 9.19 | 9.08 | 8.96 | 8.83 | 8.83 | 9.33 | 10.05 | 9.75 | 9.64 | 9.49 | 9.26 |
| 5 | 11.31 | 11.17 | 11.09 | 12.26 | 12.15 | 12.00 | 11.84 | 11.80 | 12.47 | 13.43 | 13.01 | 12.86 | 12.64 | 12.32 |
| 6 | 13.96 | 13.93 | 13.94 | 15.51 | 15.42 | 15.29 | 15.10 | 15.04 | 15.89 | 17.10 | 16.54 | 16.34 | 16.04 | 15.59 |
| 7 | 16.47 | 16.63 | 16.79 | 18.81 | 18.83 | 18.73 | 18.55 | 18.48 | 19.52 | 21.03 | 20.33 | 20.07 | 19.69 | 19.09 |
| 8 | 18.87 | 19.25 | 19.61 | 22.06 | 22.21 | 22.20 | 22.08 | 22.03 | 23.28 | 25.11 | 24.30 | 23.98 | 23.52 | 22.78 |
| 9 | 23.44 | 24.05 | 24.70 | 25.30 | 25.61 | 25.72 | 25.67 | 25.66 | 27.14 | 29.30 | 28.42 | 28.06 | 27.53 | 26.66 |
| 10 | 25.53 | 26.49 | 27.38 | 28.19 | 28.70 | 29.01 | 29.16 | 29.33 | 31.05 | 33.56 | 32.61 | 32.21 | 31.62 | 30.65 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.50 | 8.29 | 8.16 | 8.09 | 8.00 | 7.91 | 7.81 | 7.84 | 8.30 | 8.96 | 8.72 | 8.63 | 8.51 | 8.32 |
| 5 | 9.92 | 9.76 | 9.66 | 10.68 | 10.59 | 10.48 | 10.34 | 10.34 | 10.94 | 11.79 | 11.45 | 11.33 | 11.15 | 10.89 |
| 6 | 12.24 | 12.13 | 12.07 | 13.42 | 13.35 | 13.23 | 13.07 | 13.04 | 13.79 | 14.86 | 14.39 | 14.22 | 13.98 | 13.60 |
| 7 | 14.48 | 14.49 | 14.55 | 16.24 | 16.21 | 16.11 | 15.95 | 15.91 | 16.81 | 18.12 | 17.53 | 17.31 | 16.99 | 16.49 |
| 8 | 16.64 | 16.81 | 16.99 | 19.08 | 19.14 | 19.08 | 18.94 | 18.88 | 19.96 | 21.52 | 20.83 | 20.55 | 20.16 | 19.52 |
| 9 | 20.77 | 21.18 | 21.57 | 21.86 | 22.03 | 22.05 | 21.95 | 21.92 | 23.18 | 25.00 | 24.22 | 23.90 | 23.44 | 22.68 |
| 10 | 22.93 | 23.51 | 24.11 | 24.64 | 24.92 | 25.03 | 24.99 | 25.01 | 26.46 | 28.56 | 27.71 | 27.36 | 26.83 | 25.95 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 32.605 | 27.712 |
| SC2 | 0 | 8 | 22.026 | 18.881 |
| SC3 | -18 | 7 | 18.834 | 16.245 |
| SC4 | -25 | 6 | 13.935 | 12.074 |
| SC5 | -34 | 6 | 13.970 | 12.231 |
| A | 1725 mm |
|---|---|
| B | 1000 mm |
| C | 1150 mm |
| F | 960 mm |
| G | 1540 mm |
| E | 1335 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 1725 mm |
|---|---|
| Width | 1540 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.