EK-T-250AE10-B10 C
19.84 kW
Defrost: None
Product code: EK-T-163BG10-B08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 13,805 m³/h |
|---|---|
| External surface | 73.2 m² |
| Inner volume | 31.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 206 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EK-T-163BG10-B08 C | None |
|---|---|
| EK-T-163BG10-B08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.33 | 9.01 | 8.81 | 8.68 | 8.55 | 8.42 | 8.29 | 8.40 | 8.87 | 9.57 | 9.32 | 9.22 | 9.09 | 8.90 |
| 5 | 11.07 | 10.77 | 10.58 | 11.61 | 11.44 | 11.25 | 11.04 | 11.10 | 11.76 | 12.67 | 12.30 | 12.17 | 12.00 | 11.74 |
| 6 | 13.84 | 13.56 | 13.40 | 14.77 | 14.58 | 14.35 | 14.08 | 14.08 | 14.89 | 16.02 | 15.48 | 15.29 | 15.03 | 14.64 |
| 7 | 16.58 | 16.42 | 16.33 | 18.06 | 17.90 | 17.65 | 17.34 | 17.30 | 18.26 | 19.64 | 18.92 | 18.66 | 18.28 | 17.71 |
| 8 | 19.26 | 19.24 | 19.27 | 21.46 | 21.35 | 21.10 | 20.77 | 20.68 | 21.83 | 23.47 | 22.58 | 22.24 | 21.75 | 20.99 |
| 9 | 24.26 | 24.46 | 24.67 | 24.86 | 24.84 | 24.65 | 24.32 | 24.21 | 25.54 | 27.46 | 26.41 | 26.00 | 25.40 | 24.43 |
| 10 | 27.00 | 27.46 | 27.81 | 28.19 | 28.28 | 28.17 | 27.88 | 27.79 | 29.33 | 31.56 | 30.39 | 29.91 | 29.21 | 28.07 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.07 | 7.80 | 7.65 | 7.56 | 7.47 | 7.38 | 7.28 | 7.39 | 7.86 | 8.49 | 8.29 | 8.21 | 8.11 | 7.95 |
| 5 | 9.50 | 9.23 | 9.07 | 9.98 | 9.85 | 9.71 | 9.56 | 9.63 | 10.21 | 11.03 | 10.73 | 10.62 | 10.48 | 10.28 |
| 6 | 11.80 | 11.55 | 11.40 | 12.57 | 12.42 | 12.24 | 12.04 | 12.07 | 12.77 | 13.77 | 13.32 | 13.17 | 12.95 | 12.63 |
| 7 | 14.16 | 13.91 | 13.80 | 15.27 | 15.13 | 14.93 | 14.68 | 14.67 | 15.50 | 16.69 | 16.10 | 15.89 | 15.58 | 15.11 |
| 8 | 16.46 | 16.32 | 16.27 | 18.05 | 17.94 | 17.74 | 17.46 | 17.41 | 18.38 | 19.78 | 19.05 | 18.77 | 18.37 | 17.74 |
| 9 | 20.79 | 20.76 | 20.81 | 20.89 | 20.82 | 20.62 | 20.34 | 20.25 | 21.37 | 23.00 | 22.14 | 21.79 | 21.29 | not rated |
| 10 | 23.20 | 23.35 | 23.54 | 23.73 | 23.71 | 23.55 | 23.26 | 23.18 | 24.46 | 26.30 | 25.34 | 24.93 | 24.34 | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 30.391 | 25.335 |
| SC2 | 0 | 8 | 20.683 | 17.407 |
| SC3 | -18 | 7 | 18.010 | 15.224 |
| SC4 | -25 | 6 | 13.396 | 11.396 |
| SC5 | -34 | 6 | 13.768 | 11.759 |
| A | 1460 mm |
|---|---|
| B | 1200 mm |
| C | 1035 mm |
| F | 940 mm |
| G | 1035 mm |
| E | 1150 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 1460 mm |
|---|---|
| Width | 1200 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.