EK-T-250AE10-B10 C
19.84 kW
Defrost: None
Product code: EK-T-163BE10-B13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 16,958 m³/h |
|---|---|
| External surface | 54.9 m² |
| Inner volume | 23.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 185 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.1 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EK-T-163BE10-B13 C | None |
|---|---|
| EK-T-163BE10-B13 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.91 | 7.62 | 7.43 | 7.29 | 7.16 | 7.03 | 6.90 | 6.89 | 7.26 | 7.82 | 7.58 | 7.50 | 7.38 | 7.20 |
| 5 | 9.49 | 9.24 | 9.07 | 9.93 | 9.76 | 9.57 | 9.38 | 9.34 | 9.86 | 10.60 | 10.25 | 10.12 | 9.93 | 9.66 |
| 6 | 11.95 | 11.76 | 11.63 | 12.80 | 12.62 | 12.41 | 12.17 | 12.09 | 12.75 | 13.69 | 13.20 | 13.03 | 12.78 | 12.41 |
| 7 | 14.35 | 14.29 | 14.26 | 15.82 | 15.68 | 15.46 | 15.19 | 15.08 | 15.91 | 17.08 | 16.44 | 16.21 | 15.88 | 15.37 |
| 8 | 16.67 | 16.78 | 16.90 | 18.88 | 18.82 | 18.65 | 18.39 | 18.25 | 19.25 | 20.69 | 19.91 | 19.62 | 19.20 | 18.55 |
| 9 | 20.95 | 21.26 | 21.60 | 21.88 | 21.95 | 21.86 | 21.65 | 21.55 | 22.74 | 24.47 | 23.58 | 23.23 | 22.73 | 21.93 |
| 10 | 22.98 | 23.56 | 24.12 | 24.63 | 24.93 | 25.06 | 24.98 | 24.91 | 26.32 | 28.36 | 27.38 | 26.99 | 26.42 | 25.49 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.86 | 6.62 | 6.47 | 6.38 | 6.28 | 6.18 | 6.09 | 6.15 | 6.49 | 7.00 | 6.82 | 6.75 | 6.65 | 6.51 |
| 5 | 8.18 | 7.94 | 7.79 | 8.55 | 8.42 | 8.28 | 8.13 | 8.16 | 8.64 | 9.31 | 9.04 | 8.95 | 8.82 | 8.61 |
| 6 | 10.23 | 10.03 | 9.90 | 10.90 | 10.76 | 10.59 | 10.39 | 10.39 | 10.98 | 11.82 | 11.42 | 11.29 | 11.10 | 10.81 |
| 7 | 12.33 | 12.18 | 12.10 | 13.38 | 13.25 | 13.06 | 12.83 | 12.80 | 13.51 | 14.53 | 14.01 | 13.82 | 13.55 | 13.14 |
| 8 | 14.35 | 14.32 | 14.32 | 15.93 | 15.84 | 15.65 | 15.41 | 15.35 | 16.20 | 17.42 | 16.76 | 16.52 | 16.17 | 15.62 |
| 9 | 18.11 | 18.24 | 18.37 | 18.50 | 18.48 | 18.33 | 18.09 | 18.00 | 19.00 | 20.45 | 19.68 | 19.37 | 18.93 | 18.24 |
| 10 | 20.19 | 20.51 | 20.75 | 21.02 | 21.09 | 21.01 | 20.80 | 20.72 | 21.88 | 23.54 | 22.68 | 22.34 | 21.83 | 21.01 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 27.383 | 22.682 |
| SC2 | 0 | 8 | 18.254 | 15.346 |
| SC3 | -18 | 7 | 15.772 | 13.333 |
| SC4 | -25 | 6 | 11.630 | 9.900 |
| SC5 | -34 | 6 | 11.929 | 10.201 |
| A | 1460 mm |
|---|---|
| B | 1158 mm |
| C | 1035 mm |
| F | 840 mm |
| G | 1035 mm |
| E | 1150 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 1460 mm |
|---|---|
| Width | 1158 mm |
| Height | 1150 mm |