EK-T-163BE10-B13 C
18.25 kW
Defrost: None
Product code: EK-T-163BE10-B08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 14,872 m³/h |
|---|---|
| External surface | 54.9 m² |
| Inner volume | 23.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 183 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EK-T-163BE10-B08 C | None |
|---|---|
| EK-T-163BE10-B08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.32 | 7.05 | 6.87 | 6.76 | 6.65 | 6.53 | 6.43 | 6.44 | 6.80 | 7.32 | 7.12 | 7.04 | 6.94 | 6.78 |
| 5 | 8.76 | 8.52 | 8.35 | 9.14 | 8.99 | 8.82 | 8.65 | 8.66 | 9.15 | 9.84 | 9.54 | 9.43 | 9.27 | 9.03 |
| 6 | 11.03 | 10.80 | 10.66 | 11.74 | 11.57 | 11.37 | 11.15 | 11.12 | 11.74 | 12.62 | 12.18 | 12.03 | 11.81 | 11.49 |
| 7 | 13.27 | 13.15 | 13.08 | 14.48 | 14.33 | 14.12 | 13.86 | 13.80 | 14.57 | 15.65 | 15.07 | 14.86 | 14.56 | 14.12 |
| 8 | 15.44 | 15.47 | 15.51 | 17.28 | 17.19 | 17.00 | 16.72 | 16.64 | 17.56 | 18.87 | 18.15 | 17.88 | 17.50 | 16.90 |
| 9 | 19.47 | 19.70 | 19.91 | 20.05 | 20.06 | 19.92 | 19.68 | 19.59 | 20.67 | 22.24 | 21.39 | 21.06 | 20.59 | 19.84 |
| 10 | 21.59 | 21.98 | 22.42 | 22.83 | 22.96 | 22.90 | 22.69 | 22.62 | 23.88 | 25.70 | 24.77 | 24.40 | 23.84 | 22.95 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.43 | 6.20 | 6.06 | 5.98 | 5.90 | 5.82 | 5.74 | 5.80 | 6.13 | 6.62 | 6.45 | 6.39 | 6.30 | 6.17 |
| 5 | 7.64 | 7.42 | 7.27 | 7.98 | 7.87 | 7.74 | 7.61 | 7.65 | 8.10 | 8.74 | 8.49 | 8.41 | 8.29 | 8.11 |
| 6 | 9.56 | 9.35 | 9.22 | 10.15 | 10.02 | 9.86 | 9.69 | 9.69 | 10.25 | 11.03 | 10.68 | 10.55 | 10.38 | 10.12 |
| 7 | 11.52 | 11.35 | 11.24 | 12.43 | 12.31 | 12.13 | 11.93 | 11.90 | 12.56 | 13.51 | 13.04 | 12.87 | 12.62 | 12.25 |
| 8 | 13.43 | 13.35 | 13.32 | 14.79 | 14.68 | 14.52 | 14.29 | 14.23 | 15.02 | 16.16 | 15.56 | 15.34 | 15.02 | 14.52 |
| 9 | 16.98 | 17.02 | 17.10 | 17.18 | 17.13 | 16.98 | 16.74 | 16.67 | 17.59 | 18.93 | 18.22 | 17.94 | 17.55 | 16.92 |
| 10 | 18.97 | 19.17 | 19.38 | 19.57 | 19.57 | 19.46 | 19.25 | 19.17 | 20.23 | 21.77 | 20.98 | 20.65 | 20.18 | 19.43 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 24.772 | 20.976 |
| SC2 | 0 | 8 | 16.641 | 14.230 |
| SC3 | -18 | 7 | 14.432 | 12.386 |
| SC4 | -25 | 6 | 10.664 | 9.218 |
| SC5 | -34 | 6 | 10.998 | 9.525 |
| A | 1460 mm |
|---|---|
| B | 1100 mm |
| C | 1035 mm |
| F | 840 mm |
| G | 1035 mm |
| E | 1150 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 1460 mm |
|---|---|
| Width | 1100 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.