EA-G-450BC4-A10 C
41.45 kW
Defrost: None
Product code: EA-G-263GE10-A08 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
How to read the code of this model.
| Air flow | 32,787 m³/h |
|---|---|
| Air throw | 42 m |
| External surface | 158.7 m² |
| Inner volume | 67.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 253 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-263GE10-A08 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 12.07 | ≈ 10.95 | ≈ 10.97 | ≈ 10.97 |
| 8 | not rated | not rated | not rated | not rated | ≈ 19.65 | ≈ 26.19 | ≈ 30.21 | ≈ 32.95 |
| 10 | not rated | not rated | not rated | not rated | 38.43 | 41.42 | 44.43 | 48.77 |
| 12 | not rated | not rated | not rated | not rated | not rated | 54.44 | 58.45 | 63.70 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 11.28 | 10.09 | ≈ 10.10 | ≈ 10.08 |
| 8 | not rated | not rated | not rated | not rated | 18.22 | ≈ 17.06 | ≈ 26.24 | ≈ 28.94 |
| 10 | not rated | not rated | not rated | not rated | ≈ 25.31 | 35.90 | 39.00 | 42.96 |
| 12 | not rated | not rated | not rated | not rated | not rated | 47.48 | 51.31 | 56.07 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 41.423 | 13.01 | 71.6 |
| Low speed (Y) | 35.903 | 11.28 | 55.6 |
| A | 3015 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| G | 1035 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3015 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.