Skip to Content

Brine cooler EA-G-280GE7-A01 C

Brine cooler EA-G-280GE7-A01 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-280GE7-A01 C

Cooling capacity i
58.37 kW
Air flow
39,176 m³/h
Fin spacing
7.0 mm
Air throw
40 m
Fans
2 × ⌀800 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 39,176 m³/h
Air throw 40 m
External surface 263.6 m²
Inner volume 85.0 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 354 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 83.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
EA-G-280GE7-A01 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
58.373 kW Sensible capacity 42.472 kW Fluid flow 18.33 m³/h Pressure drop 90.4 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
48.267 kW Sensible capacity 34.980 kW Fluid flow 15.16 m³/h Pressure drop 64.6 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 15.66 ≈ 14.49 ≈ 14.55 ≈ 21.35
8 not rated not rated not rated not rated ≈ 25.68 ≈ 38.48 ≈ 42.63 ≈ 45.72
10 not rated not rated not rated not rated ≈ 55.34 58.37 61.82 67.29
12 not rated not rated not rated not rated not rated 76.24 81.10 87.78

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 14.34 ≈ 13.02 ≈ 13.05 ≈ 13.01
8 not rated not rated not rated not rated ≈ 23.26 ≈ 30.46 ≈ 34.89 ≈ 38.39
10 not rated not rated not rated not rated 44.46 48.27 51.73 56.56
12 not rated not rated not rated not rated not rated 63.33 67.90 73.70

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 58.373 18.33 90.4
Low speed (Y) 48.267 15.16 64.6

Dimensions

Dimension drawing of EA-G-280GE7-A01 C
Dimension drawing
Dimensions as drawn
A 3015 mm
B 1050 mm
C 1430 mm
F 1010 mm
G 1115 mm
E1 1318 mm
E 2635 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3015 mm
Width 1050 mm
Height 1430 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.