EA-G-363GC4-A08 C
58.03 kW
Defrost: None
Product code: EA-G-463ED4-A11 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 58,640 m³/h |
|---|---|
| Air throw | 42 m |
| External surface | 334.1 m² |
| Inner volume | 72.6 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 343 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 10,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 73.0 dB(A) |
|---|---|
| Sound power | 96.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-463ED4-A11 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 12.79 | 12.94 | ≈ 13.05 | ≈ 13.11 |
| 8 | not rated | not rated | not rated | not rated | 21.08 | ≈ 21.30 | ≈ 37.29 | ≈ 45.72 |
| 10 | not rated | not rated | not rated | not rated | ≈ 30.49 | 58.08 | 66.71 | 76.41 |
| 12 | not rated | not rated | not rated | not rated | not rated | 84.96 | 93.56 | 104.14 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 12.05 | 12.20 | 12.29 | ≈ 12.32 |
| 8 | not rated | not rated | not rated | not rated | 20.01 | 19.88 | ≈ 20.00 | ≈ 38.42 |
| 10 | not rated | not rated | not rated | not rated | 28.78 | 28.07 | ≈ 56.85 | ≈ 66.13 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 71.87 | 80.56 | 90.32 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 58.081 | 18.24 | 32.7 |
| Low speed (Y) | 28.074 | 8.82 | 8.9 |
| A | 3615 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 3235 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3615 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.