Skip to Content

Brine cooler EA-G-463FC4-A19 C

Brine cooler EA-G-463FC4-A19 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-463FC4-A19 C

Cooling capacity i
58.35 kW
Air flow
47,119 m³/h
Fin spacing
4.6 mm
Air throw
32 m
Fans
4 × ⌀630 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 47,119 m³/h
Air throw 32 m
External surface 334.1 m²
Inner volume 68.8 dm³
Fin spacing 4.6 mm
Fin materialAluminium
Net weight 343 kg
Fans
Quantity 4
Diameter 630 mm
Speed 1,330 rpm
Power 5,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 67.0 dB(A)
Sound power 90.0 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
EA-G-463FC4-A19 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
58.354 kW Sensible capacity 42.669 kW Fluid flow 18.33 m³/h Pressure drop 65.8 kPa
Cooling capacity · Low speed (Y)
50.898 kW Sensible capacity 37.118 kW Fluid flow 15.98 m³/h Pressure drop 51.5 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 11.90 12.01 ≈ 12.08 ≈ 12.14
8 not rated not rated not rated not rated ≈ 19.79 ≈ 19.59 ≈ 40.73 ≈ 45.54
10 not rated not rated not rated not rated ≈ 51.95 58.35 63.37 70.60
12 not rated not rated not rated not rated not rated 79.18 85.57 94.08

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 11.29 11.39 ≈ 11.45 ≈ 11.49
8 not rated not rated not rated not rated 18.89 ≈ 18.43 ≈ 35.40 ≈ 40.38
10 not rated not rated not rated not rated ≈ 27.03 50.90 56.14 62.86
12 not rated not rated not rated not rated not rated 69.72 75.94 83.74

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 58.354 18.33 65.8
Low speed (Y) 50.898 15.98 51.5

Dimensions

Dimension drawing of EA-G-463FC4-A19 C
Dimension drawing
Dimensions as drawn
A 4415 mm
B 900 mm
C 1190 mm
F 860 mm
E1 1018 mm
E2 1000 mm
E 4035 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 4415 mm
Width 900 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.