EA-G-563FE10-A19 C
69.82 kW
Defrost: None
Product code: EA-G-363EG4-A11 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 37,255 m³/h |
|---|---|
| Air throw | 35 m |
| External surface | 400.5 m² |
| Inner volume | 83.4 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 334 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 74.0 dB(A) |
|---|---|
| Sound power | 96.5 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-363EG4-A11 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 16.82 | 16.04 | ≈ 16.15 | ≈ 16.16 |
| 8 | not rated | not rated | not rated | not rated | 28.18 | ≈ 25.87 | ≈ 47.65 | ≈ 54.96 |
| 10 | not rated | not rated | not rated | not rated | ≈ 40.20 | 69.78 | 76.61 | 85.29 |
| 12 | not rated | not rated | not rated | not rated | not rated | 95.37 | 103.45 | 113.46 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 15.77 | 14.76 | ≈ 14.83 | ≈ 14.81 |
| 8 | not rated | not rated | not rated | not rated | 26.12 | ≈ 24.13 | ≈ 37.18 | ≈ 45.94 |
| 10 | not rated | not rated | not rated | not rated | ≈ 36.96 | 56.45 | 64.02 | not rated |
| 12 | not rated | not rated | not rated | not rated | not rated | 78.99 | 86.79 | not rated |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 69.782 | 21.91 | 48.6 |
| Low speed (Y) | 56.447 | 17.73 | 33.3 |
| A | 2815 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 2815 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.