EA-G-563FD10-A08 C
69.83 kW
Defrost: None
Product code: EA-G-563FE10-A19 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 58,914 m³/h |
|---|---|
| Air throw | 34 m |
| External surface | 305.2 m² |
| Inner volume | 131.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 477 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,250 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 67.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| EA-G-563FE10-A19 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 17.96 | 17.62 | ≈ 17.67 | ≈ 17.68 |
| 8 | not rated | not rated | not rated | not rated | 29.52 | ≈ 28.04 | ≈ 50.03 | ≈ 56.11 |
| 10 | not rated | not rated | not rated | not rated | ≈ 41.62 | 69.82 | 76.45 | 84.75 |
| 12 | not rated | not rated | not rated | not rated | not rated | 93.65 | 101.60 | 111.42 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 16.99 | 16.43 | ≈ 16.47 | ≈ 16.45 |
| 8 | not rated | not rated | not rated | not rated | 27.73 | ≈ 25.96 | ≈ 42.68 | ≈ 49.22 |
| 10 | not rated | not rated | not rated | not rated | ≈ 38.89 | 59.95 | 67.09 | 74.86 |
| 12 | not rated | not rated | not rated | not rated | not rated | 81.70 | 89.47 | 98.45 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 69.819 | 21.93 | 46.8 |
| Low speed (Y) | 59.953 | 18.83 | 35.8 |
| A | 5415 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5415 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.