EA-G-563FE10-A19 C
69.82 kW
Defrost: None
Product code: EA-G-563FD10-A08 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 78,998 m³/h |
|---|---|
| Air throw | 46 m |
| External surface | 254.3 m² |
| Inner volume | 108.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 443 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 9,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-563FD10-A08 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 15.98 | ≈ 16.02 | ≈ 16.09 | ≈ 16.12 |
| 8 | not rated | not rated | not rated | not rated | ≈ 26.53 | ≈ 42.19 | ≈ 50.13 | ≈ 54.93 |
| 10 | not rated | not rated | not rated | not rated | ≈ 64.13 | 69.83 | 74.95 | 82.55 |
| 12 | not rated | not rated | not rated | not rated | not rated | 92.66 | 99.46 | 108.50 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 15.20 | 15.02 | ≈ 15.08 | ≈ 15.08 |
| 8 | not rated | not rated | not rated | not rated | 25.05 | ≈ 23.98 | ≈ 43.61 | ≈ 48.51 |
| 10 | not rated | not rated | not rated | not rated | ≈ 35.38 | 60.86 | 66.23 | 73.16 |
| 12 | not rated | not rated | not rated | not rated | not rated | 81.39 | 87.94 | 96.16 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 69.829 | 21.94 | 66.2 |
| Low speed (Y) | 60.863 | 19.11 | 51.8 |
| A | 5415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| G | 985 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5415 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.