EA-G-480GC4-A01 C
108.52 kW
Defrost: None
Product code: EA-G-380GG7-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
How to read the code of this model.
| Air flow | 53,785 m³/h |
|---|---|
| Air throw | 39 m |
| External surface | 527.3 m² |
| Inner volume | 163.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 592 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| EA-G-380GG7-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | ≈ 27.67 | ≈ 25.53 | ≈ 25.62 | ≈ 40.47 |
| 8 | not rated | not rated | not rated | not rated | ≈ 69.26 | ≈ 73.98 | ≈ 79.27 | ≈ 85.77 |
| 10 | not rated | not rated | not rated | not rated | 103.62 | 108.53 | 114.64 | 124.10 |
| 12 | not rated | not rated | not rated | not rated | not rated | 140.17 | 148.89 | 160.60 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 25.22 | ≈ 22.76 | ≈ 22.79 | ≈ 22.70 |
| 8 | not rated | not rated | not rated | not rated | ≈ 40.73 | ≈ 58.68 | ≈ 64.23 | ≈ 70.90 |
| 10 | not rated | not rated | not rated | not rated | ≈ 82.50 | 88.30 | 94.28 | 102.48 |
| 12 | not rated | not rated | not rated | not rated | not rated | 114.30 | 122.34 | 132.36 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 108.528 | 34.08 | 108.8 |
| Low speed (Y) | 88.300 | 27.74 | 75.5 |
| A | 4315 mm |
|---|---|
| B | 1150 mm |
| C | 1430 mm |
| F | 1110 mm |
| G | 1215 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 3935 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4315 mm |
|---|---|
| Width | 1150 mm |
| Height | 1430 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.