EA-G-480GC4-A01 C
108.52 kW
Defrost: None
Product code: EA-G-563FE4-A19 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 55,308 m³/h |
|---|---|
| Air throw | 32 m |
| External surface | 626.5 m² |
| Inner volume | 131.4 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 524 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,250 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| EA-G-563FE4-A19 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | ≈ 21.24 | ≈ 21.43 | ≈ 21.54 | ≈ 42.18 |
| 8 | not rated | not rated | not rated | not rated | ≈ 64.17 | ≈ 71.32 | ≈ 77.93 | ≈ 85.28 |
| 10 | not rated | not rated | not rated | not rated | 102.59 | 108.38 | 115.36 | 126.08 |
| 12 | not rated | not rated | not rated | not rated | not rated | 141.86 | 151.69 | 164.89 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 20.19 | ≈ 20.06 | ≈ 20.15 | ≈ 34.76 |
| 8 | not rated | not rated | not rated | not rated | ≈ 33.54 | ≈ 60.03 | ≈ 67.01 | ≈ 74.39 |
| 10 | not rated | not rated | not rated | not rated | ≈ 86.87 | 93.36 | 100.18 | 109.82 |
| 12 | not rated | not rated | not rated | not rated | not rated | 122.37 | 131.62 | 143.26 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 108.378 | 34.03 | 102.2 |
| Low speed (Y) | 93.357 | 29.32 | 78.5 |
| A | 5415 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5415 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.