EA-G-380GG7-A01 C
108.53 kW
Defrost: None
Product code: EA-G-480GC4-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 81,728 m³/h |
|---|---|
| Air throw | 45 m |
| External surface | 521.3 m² |
| Inner volume | 109.8 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 591 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-480GC4-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | ≈ 18.98 | ≈ 19.17 | ≈ 41.06 | 44.38 |
| 8 | not rated | not rated | not rated | not rated | ≈ 70.69 | ≈ 72.93 | 78.80 | 83.77 |
| 10 | not rated | not rated | not rated | not rated | 104.71 | 108.52 | 113.95 | 123.78 |
| 12 | not rated | not rated | not rated | not rated | not rated | 141.60 | 149.85 | 161.97 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | ≈ 17.66 | ≈ 17.85 | ≈ 32.29 | 36.30 |
| 8 | not rated | not rated | not rated | not rated | ≈ 56.90 | ≈ 61.02 | ≈ 66.79 | 71.57 |
| 10 | not rated | not rated | not rated | not rated | 87.34 | 91.65 | 96.98 | 105.56 |
| 12 | not rated | not rated | not rated | not rated | not rated | 119.66 | 127.34 | 137.92 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 108.517 | 34.08 | 160.7 |
| Low speed (Y) | 91.652 | 28.78 | 119.0 |
| A | 5615 mm |
|---|---|
| B | 950 mm |
| C | 1430 mm |
| F | 910 mm |
| G | 1015 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 5235 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5615 mm |
|---|---|
| Width | 950 mm |
| Height | 1430 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.