BC/BD-t-280GC5-B01 C
100.10 kW
Defrost: None
Product code: BC/BD-2X180AC1-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 31,099 m³/h |
|---|---|
| External surface | 329.5 m² |
| Inner volume | 52.7 dm³ |
| Fin material | Aluminium |
| Net weight | 374 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 3,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 86.5 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-2X180AC1-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 57.12 | not rated | not rated | not rated | not rated | not rated |
| 40 | 100.01 | 57.53 | not rated | not rated | not rated | not rated |
| 45 | 141.76 | 100.15 | 57.90 | not rated | not rated | not rated |
| 50 | 183.14 | 141.68 | 100.30 | 58.24 | not rated | not rated |
| 55 | 224.34 | 182.85 | 141.65 | 100.48 | 58.58 | not rated |
| 60 | 265.44 | 223.86 | 182.66 | 141.71 | 100.74 | 58.95 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 100.011 | 17.36 | 34.1 |
| A | 1550 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1300 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 1850 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 1550 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.