Skip to Content

Dry cooler BC/BD-t-280GC5-B01 C

Dry cooler BC/BD-t-280GC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-280GC5-B01 C

Heat rejection i
100.10 kW
Air flow
30,008 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 30,008 m³/h
External surface 183.9 m²
Inner volume 30.5 dm³
Fin materialAluminium
Net weight 326 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 85.8 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-t-280GC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
100.103 kW Fluid flow 17.37 m³/h Pressure drop 59.2 kPa
Heat rejection · Low speed (Y)
77.736 kW Fluid flow 13.49 m³/h Pressure drop 37.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 57.97 not rated not rated not rated not rated not rated
40 100.10 58.34 not rated not rated not rated not rated
45 141.14 100.27 58.67 not rated not rated not rated
50 181.82 141.13 100.45 59.01 not rated not rated
55 222.31 181.65 141.19 100.68 59.36 not rated
60 262.72 222.00 181.58 141.35 101.00 59.75

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 45.51 not rated not rated not rated not rated not rated
40 77.74 45.79 not rated not rated not rated not rated
45 108.99 77.83 46.06 not rated not rated not rated
50 139.94 108.96 77.97 46.32 not rated not rated
55 170.73 139.78 108.99 78.15 46.65 not rated
60 201.45 170.46 139.73 109.13 78.48 46.98

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 100.103 17.37 59.2
Low speed (Y) 77.736 13.49 37.9

Dimensions

Dimension drawing of BC/BD-t-280GC5-B01 C
Dimension drawing
Dimensions as drawn
A 2450 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 2200 mm
H 1050 mm
I 1180 mm
K 2750 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2450 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.