Skip to Content

Dry cooler BC/BD-380KB1-B03 C

Dry cooler BC/BD-380KB1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-380KB1-B03 C

Heat rejection i
99.90 kW
Air flow
29,957 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 29,957 m³/h
External surface 407.1 m²
Inner volume 44.3 dm³
Fin materialAluminium
Net weight 553 kg
Fans
Quantity 3
Diameter 800 mm
Speed 435 rpm
Power 1,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 37.0 dB(A)
Sound power 69.0 dB(A)
Energy class C
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-380KB1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
99.896 kW Fluid flow 17.34 m³/h Pressure drop 48.5 kPa
Heat rejection · Low speed (Y)
78.854 kW Fluid flow 13.68 m³/h Pressure drop 31.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 58.56 not rated not rated not rated not rated not rated
40 99.90 58.71 not rated not rated not rated not rated
45 140.17 99.75 58.84 not rated not rated not rated
50 180.09 139.75 99.62 58.97 not rated not rated
55 219.85 179.42 139.40 99.54 59.12 not rated
60 259.52 218.94 178.86 139.16 99.55 59.30

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 46.54 not rated not rated not rated not rated not rated
40 78.85 46.70 not rated not rated not rated not rated
45 110.23 78.79 46.85 not rated not rated not rated
50 141.31 109.97 78.75 47.00 not rated not rated
55 172.25 140.89 109.79 78.75 47.17 not rated
60 203.12 171.67 140.56 109.69 78.83 47.37

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 99.896 17.34 48.5
Low speed (Y) 78.854 13.68 31.8

Dimensions

Dimension drawing of BC/BD-380KB1-B03 C
Dimension drawing
Dimensions as drawn
A 5600 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1750 mm
I 1180 mm
K 5900 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 5900 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.