BC/BD-2X363CB1-B19 C
192.49 kW
Defrost: None
Product code: BC/BD-2X280AC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 67,482 m³/h |
|---|---|
| External surface | 557.2 m² |
| Inner volume | 93.1 dm³ |
| Fin material | Aluminium |
| Net weight | 654 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X280AC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 108.92 | not rated | not rated | not rated | not rated | not rated |
| 40 | 192.61 | 109.83 | not rated | not rated | not rated | not rated |
| 45 | 274.35 | 193.09 | 110.63 | not rated | not rated | not rated |
| 50 | 355.43 | 274.47 | 193.54 | 111.35 | not rated | not rated |
| 55 | 436.24 | 355.25 | 274.62 | 194.02 | 112.08 | not rated |
| 60 | 516.87 | 435.74 | 355.14 | 274.91 | 194.61 | 112.83 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 87.82 | not rated | not rated | not rated | not rated | not rated |
| 40 | 153.96 | 88.50 | not rated | not rated | not rated | not rated |
| 45 | 218.26 | 154.21 | 89.12 | not rated | not rated | not rated |
| 50 | 281.97 | 218.18 | 154.48 | 89.68 | not rated | not rated |
| 55 | 345.41 | 281.58 | 218.19 | 154.80 | 90.25 | not rated |
| 60 | 408.70 | 344.74 | 281.35 | 218.32 | 155.23 | 90.85 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 192.611 | 33.43 | 32.5 |
| Low speed (Y) | 153.957 | 26.72 | 21.7 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 3050 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 2750 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.