BC/BD-t-2x280LC1-B03 C
192.42 kW
Defrost: None
Product code: BC/BD-2X363CB1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 69,788 m³/h |
|---|---|
| External surface | 556.0 m² |
| Inner volume | 82.5 dm³ |
| Fin material | Aluminium |
| Net weight | 563 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X363CB1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 109.39 | not rated | not rated | not rated | not rated | not rated |
| 40 | 192.49 | 110.01 | not rated | not rated | not rated | not rated |
| 45 | 273.84 | 192.61 | 110.55 | not rated | not rated | not rated |
| 50 | 354.62 | 273.52 | 192.72 | 111.03 | not rated | not rated |
| 55 | 435.13 | 353.87 | 273.24 | 192.87 | 111.50 | not rated |
| 60 | 515.50 | 433.98 | 353.22 | 273.08 | 193.09 | 112.00 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 94.17 | not rated | not rated | not rated | not rated | not rated |
| 40 | 164.70 | 94.68 | not rated | not rated | not rated | not rated |
| 45 | 233.57 | 164.75 | 95.12 | not rated | not rated | not rated |
| 50 | 301.91 | 233.21 | 164.80 | 95.53 | not rated | not rated |
| 55 | 369.99 | 301.17 | 232.94 | 164.92 | 95.95 | not rated |
| 60 | 437.93 | 368.89 | 300.56 | 232.78 | 165.12 | 96.40 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 192.494 | 33.41 | 54.0 |
| Low speed (Y) | 164.703 | 28.59 | 40.9 |
| A | 3000 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 3300 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3300 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.