BC/BD-2X280AC5-B01 C
192.61 kW
Defrost: None
Product code: BC/BD-580HB1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 84,436 m³/h |
|---|---|
| External surface | 407.1 m² |
| Inner volume | 61.3 dm³ |
| Fin material | Aluminium |
| Net weight | 718 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 9,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-580HB1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 104.58 | not rated | not rated | not rated | not rated | not rated |
| 40 | 192.77 | 106.13 | not rated | not rated | not rated | not rated |
| 45 | 278.83 | 193.82 | 107.47 | not rated | not rated | not rated |
| 50 | 364.29 | 279.56 | 194.78 | 108.67 | not rated | not rated |
| 55 | 449.46 | 364.74 | 280.27 | 195.71 | 109.78 | not rated |
| 60 | 534.50 | 449.66 | 365.23 | 281.04 | 196.66 | 110.85 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 84.75 | not rated | not rated | not rated | not rated | not rated |
| 40 | 155.42 | 86.03 | not rated | not rated | not rated | not rated |
| 45 | 224.02 | 156.20 | 87.14 | not rated | not rated | not rated |
| 50 | 292.03 | 224.48 | 156.91 | 88.12 | not rated | not rated |
| 55 | 359.75 | 292.22 | 224.95 | 157.62 | 89.02 | not rated |
| 60 | 427.32 | 359.70 | 292.48 | 225.49 | 158.36 | 89.90 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 192.768 | 33.46 | 19.7 |
| Low speed (Y) | 155.419 | 26.97 | 13.4 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 5900 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5600 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.