BC/BD-291GD1-B04 C
193.15 kW
Defrost: None
Product code: BC/BD-t-480GB1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 63,536 m³/h |
|---|---|
| External surface | 325.7 m² |
| Inner volume | 53.6 dm³ |
| Fin material | Aluminium |
| Net weight | 582 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-t-480GB1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 110.68 | not rated | not rated | not rated | not rated | not rated |
| 40 | 192.98 | 111.41 | not rated | not rated | not rated | not rated |
| 45 | 273.38 | 193.35 | 112.08 | not rated | not rated | not rated |
| 50 | 353.17 | 273.45 | 193.74 | 112.74 | not rated | not rated |
| 55 | 432.67 | 352.94 | 273.61 | 194.22 | 113.41 | not rated |
| 60 | 512.00 | 432.17 | 352.89 | 273.94 | 194.82 | 114.13 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 88.39 | not rated | not rated | not rated | not rated | not rated |
| 40 | 152.57 | 88.95 | not rated | not rated | not rated | not rated |
| 45 | 215.05 | 152.82 | 89.48 | not rated | not rated | not rated |
| 50 | 276.98 | 215.05 | 153.11 | 90.00 | not rated | not rated |
| 55 | 338.62 | 276.71 | 215.14 | 153.48 | 90.55 | not rated |
| 60 | 400.14 | 338.15 | 276.64 | 215.38 | 153.98 | 91.16 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 192.979 | 33.49 | 83.6 |
| Low speed (Y) | 152.566 | 26.48 | 55.2 |
| A | 4550 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4300 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 4850 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4550 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.