Dry cooler BC/BD-291GD1-B04 C

Dry cooler BC/BD-291GD1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-291GD1-B04 C

Heat rejection i
193.15 kW
Air flow
51,627 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 51,627 m³/h
External surface 823.7 m²
Inner volume 98.6 dm³
Fin materialAluminium
Net weight 609 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 62.0 dB(A)
Sound power 93.6 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-291GD1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
193.145 kW Fluid flow 33.50 m³/h Pressure drop 22.3 kPa
Heat rejection · Low speed (Y)
148.800 kW Fluid flow 25.81 m³/h Pressure drop 13.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 112.03 not rated not rated not rated not rated not rated
40 193.15 112.61 not rated not rated not rated not rated
45 271.54 192.93 113.09 not rated not rated not rated
50 349.05 270.69 192.75 113.55 not rated not rated
55 426.12 347.59 269.97 192.69 114.02 not rated
60 502.95 424.08 346.37 269.48 192.80 114.57

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 87.28 not rated not rated not rated not rated not rated
40 148.80 87.73 not rated not rated not rated not rated
45 207.95 148.60 88.12 not rated not rated not rated
50 266.30 207.24 148.46 88.49 not rated not rated
55 324.29 265.14 206.69 148.42 88.89 not rated
60 382.07 322.70 264.21 206.33 148.54 89.36

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 193.145 33.50 22.3
Low speed (Y) 148.800 25.81 13.9

Dimensions

Dimension drawing of BC/BD-291GD1-B04 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 4900 mm
H 2400 mm
I 1190 mm
K 5450 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5450 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.