Skip to Content

Dry cooler BC/BD-2X280CC5-B01 C

Dry cooler BC/BD-2X280CC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X280CC5-B01 C

Heat rejection i
246.18 kW
Air flow
77,605 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 77,605 m³/h
External surface 812.5 m²
Inner volume 141.8 dm³
Fin materialAluminium
Net weight 793 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2X280CC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
246.177 kW Fluid flow 42.73 m³/h Pressure drop 59.4 kPa
Heat rejection · Low speed (Y)
194.135 kW Fluid flow 33.69 m³/h Pressure drop 39.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 143.41 not rated not rated not rated not rated not rated
40 246.18 143.86 not rated not rated not rated not rated
45 346.55 246.00 144.26 not rated not rated not rated
50 446.15 345.82 245.88 144.66 not rated not rated
55 545.38 444.88 345.23 245.88 145.11 not rated
60 644.42 543.60 443.85 344.89 246.07 145.64

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 114.17 not rated not rated not rated not rated not rated
40 194.14 114.47 not rated not rated not rated not rated
45 272.03 193.90 114.75 not rated not rated not rated
50 349.20 271.27 193.71 115.04 not rated not rated
55 426.07 348.01 270.70 193.66 115.38 not rated
60 502.78 424.45 347.06 270.34 193.74 115.80

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 246.177 42.73 59.4
Low speed (Y) 194.135 33.69 39.0

Dimensions

Dimension drawing of BC/BD-2X280CC5-B01 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 2310 mm
K 4150 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 3850 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.