Heat rejection i
246.38 kW
Air flow
94,150 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 94,150 m³/h
External surface 363.1 m²
Inner volume 82.7 dm³
Fin materialAluminium
Net weight 631 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 97.2 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-2x291OB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
246.382 kW Fluid flow 42.76 m³/h Pressure drop 81.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
not rated

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 140.11 not rated not rated not rated not rated not rated
40 246.38 141.01 not rated not rated not rated not rated
45 350.53 246.81 141.81 not rated not rated not rated
50 454.01 350.55 247.24 142.58 not rated not rated
55 557.15 453.64 350.65 247.72 143.33 not rated
60 660.12 556.41 453.43 350.92 248.34 144.12

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 not rated not rated not rated not rated not rated not rated
40 not rated not rated not rated not rated not rated not rated
45 not rated not rated 113.84 not rated not rated not rated
50 not rated not rated 196.74 114.46 not rated not rated
55 not rated not rated 277.80 197.14 115.14 not rated
60 not rated not rated 358.29 278.04 197.73 115.84

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 246.382 42.76 81.8
Low speed (Y) — — —

Dimensions

Dimension drawing of BC/BD-t-2x291OB5-B04 C
Dimension drawing
Dimensions as drawn
A 3150 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 2900 mm
H 1400 mm
I 2260 mm
K 3450 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 3450 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.