BC/BD-2X563BB1-B01 C
246.03 kW
Defrost: None
Product code: BC/BD-480CC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 77,605 m³/h |
|---|---|
| External surface | 812.5 m² |
| Inner volume | 112.8 dm³ |
| Fin material | Aluminium |
| Net weight | 837 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-480CC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 143.26 | not rated | not rated | not rated | not rated | not rated |
| 40 | 246.03 | 143.72 | not rated | not rated | not rated | not rated |
| 45 | 346.41 | 245.86 | 144.13 | not rated | not rated | not rated |
| 50 | 446.02 | 345.68 | 245.75 | 144.53 | not rated | not rated |
| 55 | 545.25 | 444.75 | 345.11 | 245.76 | 144.99 | not rated |
| 60 | 644.29 | 543.47 | 443.73 | 344.76 | 245.95 | 145.53 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 114.05 | not rated | not rated | not rated | not rated | not rated |
| 40 | 194.03 | 114.36 | not rated | not rated | not rated | not rated |
| 45 | 271.93 | 193.80 | 114.65 | not rated | not rated | not rated |
| 50 | 349.10 | 271.17 | 193.62 | 114.95 | not rated | not rated |
| 55 | 425.98 | 347.92 | 270.61 | 193.57 | 115.28 | not rated |
| 60 | 502.69 | 424.36 | 346.97 | 270.25 | 193.65 | 115.71 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 246.032 | 42.70 | 63.1 |
| Low speed (Y) | 194.029 | 33.67 | 41.3 |
| A | 7350 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7100 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 7650 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 7350 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |