BC/BD-580DC5-B01 C
245.88 kW
Defrost: None
Product code: BC/BD-2X380HC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 95,643 m³/h |
|---|---|
| External surface | 544.7 m² |
| Inner volume | 103.2 dm³ |
| Fin material | Aluminium |
| Net weight | 822 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 89.9 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X380HC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 136.87 | not rated | not rated | not rated | not rated | not rated |
| 40 | 245.88 | 138.48 | not rated | not rated | not rated | not rated |
| 45 | 352.15 | 246.93 | 139.90 | not rated | not rated | not rated |
| 50 | 457.61 | 352.84 | 247.94 | 141.19 | not rated | not rated |
| 55 | 562.68 | 457.99 | 353.59 | 248.97 | 142.42 | not rated |
| 60 | 667.54 | 562.77 | 458.51 | 354.47 | 250.09 | 143.65 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 109.49 | not rated | not rated | not rated | not rated | not rated |
| 40 | 195.54 | 110.84 | not rated | not rated | not rated | not rated |
| 45 | 279.02 | 196.37 | 112.02 | not rated | not rated | not rated |
| 50 | 361.71 | 279.53 | 197.17 | 113.09 | not rated | not rated |
| 55 | 444.06 | 361.97 | 280.11 | 198.01 | 114.13 | not rated |
| 60 | 526.20 | 444.07 | 362.37 | 280.83 | 198.95 | 115.18 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 245.884 | 42.68 | 24.2 |
| Low speed (Y) | 195.539 | 33.93 | 16.1 |
| A | 3500 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3250 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 3800 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 3500 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.