Skip to Content

Dry cooler BC/BD-2X380HC5-B01 C

Dry cooler BC/BD-2X380HC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X380HC5-B01 C

Heat rejection i
245.88 kW
Air flow
95,643 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 95,643 m³/h
External surface 544.7 m²
Inner volume 103.2 dm³
Fin materialAluminium
Net weight 822 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 89.9 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2X380HC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
245.884 kW Fluid flow 42.68 m³/h Pressure drop 24.2 kPa
Heat rejection · Low speed (Y)
195.539 kW Fluid flow 33.93 m³/h Pressure drop 16.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 136.87 not rated not rated not rated not rated not rated
40 245.88 138.48 not rated not rated not rated not rated
45 352.15 246.93 139.90 not rated not rated not rated
50 457.61 352.84 247.94 141.19 not rated not rated
55 562.68 457.99 353.59 248.97 142.42 not rated
60 667.54 562.77 458.51 354.47 250.09 143.65

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 109.49 not rated not rated not rated not rated not rated
40 195.54 110.84 not rated not rated not rated not rated
45 279.02 196.37 112.02 not rated not rated not rated
50 361.71 279.53 197.17 113.09 not rated not rated
55 444.06 361.97 280.11 198.01 114.13 not rated
60 526.20 444.07 362.37 280.83 198.95 115.18

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 245.884 42.68 24.2
Low speed (Y) 195.539 33.93 16.1

Dimensions

Dimension drawing of BC/BD-2X380HC5-B01 C
Dimension drawing
Dimensions as drawn
A 3500 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 3250 mm
H 1050 mm
I 2260 mm
K 3800 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 3500 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.