Dry cooler BC/BD-2x480AC5-B03 C

Dry cooler BC/BD-2x480AC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x480AC5-B03 C

Heat rejection i
245.96 kW
Air flow
67,181 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 67,181 m³/h
External surface 1,114.3 m²
Inner volume 161.2 dm³
Fin materialAluminium
Net weight 1,203 kg
Fans
Quantity 8
Diameter 800 mm
Speed 435 rpm
Power 2,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 41.0 dB(A)
Sound power 73.0 dB(A)
Energy class C
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-2x480AC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
245.962 kW Fluid flow 42.69 m³/h Pressure drop 86.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
191.314 kW Fluid flow 33.18 m³/h Pressure drop 55.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 147.07 not rated not rated not rated not rated not rated
40 245.96 147.28 not rated not rated not rated not rated
45 342.36 245.60 147.53 not rated not rated not rated
50 437.98 341.56 245.42 147.82 not rated not rated
55 533.22 436.71 340.98 245.41 148.22 not rated
60 628.25 531.50 435.76 340.71 245.66 148.77

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 115.50 not rated not rated not rated not rated not rated
40 191.31 115.62 not rated not rated not rated not rated
45 265.08 190.95 115.75 not rated not rated not rated
50 338.17 264.31 190.71 115.92 not rated not rated
55 410.95 337.00 263.73 190.64 116.21 not rated
60 483.56 409.39 336.12 263.44 190.80 116.65

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 245.962 42.69 86.2
Low speed (Y) 191.314 33.18 55.0

Dimensions

Dimension drawing of BC/BD-2x480AC5-B03 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 4900 mm
H 1200 mm
I 2310 mm
K 5450 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5450 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.