Skip to Content

Dry cooler BC/BD-580DC5-B01 C

Dry cooler BC/BD-580DC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-580DC5-B01 C

Heat rejection i
245.88 kW
Air flow
79,051 m³/h
Fans
5 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 79,051 m³/h
External surface 662.4 m²
Inner volume 156.4 dm³
Fin materialAluminium
Net weight 864 kg
Fans
Quantity 5
Diameter 800 mm
Speed 900 rpm
Power 9,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-580DC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
245.876 kW Fluid flow 42.67 m³/h Pressure drop 19.0 kPa
Heat rejection · Low speed (Y)
192.485 kW Fluid flow 33.41 m³/h Pressure drop 12.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 139.75 not rated not rated not rated not rated not rated
40 245.88 140.95 not rated not rated not rated not rated
45 349.28 246.52 142.02 not rated not rated not rated
50 451.77 349.49 247.18 143.05 not rated not rated
55 553.86 451.59 349.80 247.92 144.06 not rated
60 655.71 553.29 451.60 350.32 248.81 145.14

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 110.44 not rated not rated not rated not rated not rated
40 192.49 111.39 not rated not rated not rated not rated
45 272.05 192.93 112.24 not rated not rated not rated
50 350.78 272.13 193.41 113.06 not rated not rated
55 429.17 350.54 272.32 193.99 113.89 not rated
60 507.35 428.62 350.52 272.73 194.72 114.78

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 245.876 42.67 19.0
Low speed (Y) 192.485 33.41 12.2

Dimensions

Dimension drawing of BC/BD-580DC5-B01 C
Dimension drawing
Dimensions as drawn
A 6350 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 6100 mm
H 1200 mm
I 1190 mm
K 6650 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6350 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.