BC/BD-580HB5-B01 C
174.74 kW
Defrost: None
Product code: BC/BD-2X363CB5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 70,664 m³/h |
|---|---|
| External surface | 470.1 m² |
| Inner volume | 82.5 dm³ |
| Fin material | Aluminium |
| Net weight | 549 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X363CB5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 98.83 | not rated | not rated | not rated | not rated | not rated |
| 40 | 174.84 | 99.44 | not rated | not rated | not rated | not rated |
| 45 | 249.35 | 175.02 | 99.95 | not rated | not rated | not rated |
| 50 | 323.38 | 249.15 | 175.17 | 100.42 | not rated | not rated |
| 55 | 397.21 | 322.84 | 248.99 | 175.35 | 100.87 | not rated |
| 60 | 470.91 | 396.31 | 322.37 | 248.92 | 175.60 | 101.33 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 85.74 | not rated | not rated | not rated | not rated | not rated |
| 40 | 150.87 | 86.26 | not rated | not rated | not rated | not rated |
| 45 | 214.59 | 151.00 | 86.70 | not rated | not rated | not rated |
| 50 | 277.87 | 214.38 | 151.12 | 87.11 | not rated | not rated |
| 55 | 340.93 | 277.34 | 214.23 | 151.28 | 87.51 | not rated |
| 60 | 403.88 | 340.10 | 276.92 | 214.17 | 151.50 | 87.93 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 174.842 | 30.35 | 45.5 |
| Low speed (Y) | 150.874 | 26.18 | 35.0 |
| A | 3000 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 3300 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3300 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.