BC/BD-480HD5-B01 C
184.26 kW
Defrost: None
Product code: BC/BD-2X380HA1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 110,719 m³/h |
|---|---|
| External surface | 321.5 m² |
| Inner volume | 55.3 dm³ |
| Fin material | Aluminium |
| Net weight | 744 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 88.6 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X380HA1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 100.82 | not rated | not rated | not rated | not rated | not rated |
| 40 | 184.25 | 102.01 | not rated | not rated | not rated | not rated |
| 45 | 266.29 | 185.16 | 103.06 | not rated | not rated | not rated |
| 50 | 347.96 | 267.02 | 186.01 | 104.00 | not rated | not rated |
| 55 | 429.45 | 348.53 | 267.74 | 186.83 | 104.87 | not rated |
| 60 | 510.85 | 429.87 | 349.13 | 268.48 | 187.65 | 105.71 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 83.35 | not rated | not rated | not rated | not rated | not rated |
| 40 | 151.58 | 84.31 | not rated | not rated | not rated | not rated |
| 45 | 218.53 | 152.28 | 85.16 | not rated | not rated | not rated |
| 50 | 285.08 | 219.03 | 152.92 | 85.92 | not rated | not rated |
| 55 | 351.48 | 285.41 | 219.52 | 153.54 | 86.64 | not rated |
| 60 | 417.78 | 351.66 | 285.78 | 220.05 | 154.18 | 87.32 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 184.253 | 31.98 | 48.3 |
| Low speed (Y) | 151.579 | 26.31 | 34.1 |
| A | 3500 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3250 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 3800 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3500 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.