BC/BD-480HD5-B01 C
184.26 kW
Defrost: None
Product code: BC/BD-2x191GC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 53,353 m³/h |
|---|---|
| External surface | 658.7 m² |
| Inner volume | 86.1 dm³ |
| Fin material | Aluminium |
| Net weight | 544 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.2 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-2x191GC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 108.28 | not rated | not rated | not rated | not rated | not rated |
| 40 | 184.28 | 108.47 | not rated | not rated | not rated | not rated |
| 45 | 258.39 | 183.92 | 108.64 | not rated | not rated | not rated |
| 50 | 331.86 | 257.54 | 183.63 | 108.82 | not rated | not rated |
| 55 | 405.05 | 330.52 | 256.80 | 183.44 | 109.05 | not rated |
| 60 | 478.08 | 403.24 | 329.39 | 256.27 | 183.41 | 109.36 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 86.17 | not rated | not rated | not rated | not rated | not rated |
| 40 | 145.16 | 86.31 | not rated | not rated | not rated | not rated |
| 45 | 202.53 | 144.85 | 86.44 | not rated | not rated | not rated |
| 50 | 259.36 | 201.82 | 144.60 | 86.59 | not rated | not rated |
| 55 | 315.94 | 258.27 | 201.24 | 144.45 | 86.78 | not rated |
| 60 | 372.37 | 314.47 | 257.37 | 200.83 | 144.45 | 87.05 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 184.283 | 31.98 | 86.1 |
| Low speed (Y) | 145.162 | 25.18 | 56.2 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 2310 mm |
| K | 3050 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3050 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.