Skip to Content

Dry cooler BC/BD-2X563BD1-B19 C

Dry cooler BC/BD-2X563BD1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X563BD1-B19 C

Heat rejection i
379.62 kW
Air flow
108,131 m³/h
Fans
10 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 108,131 m³/h
External surface 1,148.2 m²
Inner volume 173.4 dm³
Fin materialAluminium
Net weight 905 kg
Fans
Quantity 10
Diameter 630 mm
Speed 1,330 rpm
Power 12,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X563BD1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
379.622 kW Fluid flow 65.88 m³/h Pressure drop 45.6 kPa
Heat rejection · Low speed (Y)
312.343 kW Fluid flow 54.17 m³/h Pressure drop 32.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 221.89 not rated not rated not rated not rated not rated
40 379.62 222.73 not rated not rated not rated not rated
45 532.91 379.29 223.47 not rated not rated not rated
50 684.79 531.56 379.06 224.21 not rated not rated
55 836.01 682.52 530.50 379.05 225.01 not rated
60 986.85 832.82 680.68 529.86 379.28 225.96

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 183.87 not rated not rated not rated not rated not rated
40 312.34 184.76 not rated not rated not rated not rated
45 436.91 312.35 185.55 not rated not rated not rated
50 560.18 436.22 312.46 186.33 not rated not rated
55 682.85 558.87 435.78 312.69 187.02 not rated
60 805.19 680.94 557.91 435.61 312.96 187.85

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 379.622 65.88 45.6
Low speed (Y) 312.343 54.17 32.2

Dimensions

Dimension drawing of BC/BD-2X563BD1-B19 C
Dimension drawing
Dimensions as drawn
A 4950 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 4600 mm
H 900 mm
I 2260 mm
K 5300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 4950 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.