BC/BD-491HC1-B04 C
378.97 kW
Defrost: None
Product code: BC/BD-2x680DC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 91,147 m³/h |
|---|---|
| External surface | 1,876.5 m² |
| Inner volume | 362.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,860 kg |
| Quantity | 12 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2x680DC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 231.66 | not rated | not rated | not rated | not rated | not rated |
| 40 | 379.02 | 231.87 | not rated | not rated | not rated | not rated |
| 45 | 522.36 | 378.45 | 232.03 | not rated | not rated | not rated |
| 50 | 664.38 | 521.12 | 377.96 | 232.38 | not rated | not rated |
| 55 | 805.78 | 662.51 | 520.06 | 377.88 | 232.96 | not rated |
| 60 | 946.85 | 803.29 | 660.89 | 519.61 | 378.32 | 233.89 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 173.30 | not rated | not rated | not rated | not rated | not rated |
| 40 | 280.37 | 173.48 | not rated | not rated | not rated | not rated |
| 45 | 384.36 | 280.02 | 173.87 | not rated | not rated | not rated |
| 50 | 487.34 | 383.56 | 280.11 | 174.33 | not rated | not rated |
| 55 | 589.87 | 486.12 | 383.41 | 280.40 | 175.02 | not rated |
| 60 | 692.15 | 588.25 | 485.77 | 383.59 | 281.15 | 176.02 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 379.015 | 65.73 | 89.8 |
| Low speed (Y) | 280.372 | 48.63 | 52.6 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7300 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 7850 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 7850 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.