BC/BD-2x680DC1-B03 C
379.02 kW
Defrost: None
Product code: BC/BD-491HC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 103,204 m³/h |
|---|---|
| External surface | 1,251.0 m² |
| Inner volume | 236.5 dm³ |
| Fin material | Aluminium |
| Net weight | 1,102 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 96.6 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-491HC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 224.52 | not rated | not rated | not rated | not rated | not rated |
| 40 | 378.97 | 224.80 | not rated | not rated | not rated | not rated |
| 45 | 529.31 | 378.05 | 225.06 | not rated | not rated | not rated |
| 50 | 678.33 | 527.40 | 377.35 | 225.39 | not rated | not rated |
| 55 | 826.73 | 675.42 | 525.82 | 376.92 | 225.83 | not rated |
| 60 | 974.77 | 822.84 | 673.01 | 524.71 | 376.83 | 226.48 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 175.05 | not rated | not rated | not rated | not rated | not rated |
| 40 | 292.33 | 175.26 | not rated | not rated | not rated | not rated |
| 45 | 406.24 | 291.62 | 175.46 | not rated | not rated | not rated |
| 50 | 519.01 | 404.73 | 291.07 | 175.68 | not rated | not rated |
| 55 | 631.25 | 516.74 | 403.52 | 290.77 | 176.07 | not rated |
| 60 | 743.20 | 628.24 | 514.91 | 402.72 | 290.79 | 176.66 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 378.969 | 65.78 | 61.1 |
| Low speed (Y) | 292.325 | 50.70 | 38.4 |
| A | 9950 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 9700 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 10250 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 10250 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.