Skip to Content

Dry cooler BC/BD-2X680DC5-B01 C

Dry cooler BC/BD-2X680DC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X680DC5-B01 C

Heat rejection i
598.54 kW
Air flow
189,722 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 189,722 m³/h
External surface 1,589.8 m²
Inner volume 412.8 dm³
Fin materialAluminium
Net weight 1,856 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2X680DC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
598.542 kW Fluid flow 103.87 m³/h Pressure drop 30.7 kPa
Heat rejection · Low speed (Y)
468.169 kW Fluid flow 81.25 m³/h Pressure drop 19.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 344.60 not rated not rated not rated not rated not rated
40 598.54 346.86 not rated not rated not rated not rated
45 846.35 599.66 348.94 not rated not rated not rated
50 1092.12 846.45 600.81 350.94 not rated not rated
55 1336.92 1091.32 846.87 602.24 353.02 not rated
60 1581.22 1335.29 1091.04 847.87 604.10 355.31

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 272.17 not rated not rated not rated not rated not rated
40 468.17 273.91 not rated not rated not rated not rated
45 658.74 468.87 275.52 not rated not rated not rated
50 847.48 658.57 469.73 277.11 not rated not rated
55 1035.41 846.62 658.84 470.86 278.82 not rated
60 1222.91 1033.88 846.35 659.60 472.39 280.72

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 598.542 103.87 30.7
Low speed (Y) 468.169 81.25 19.8

Dimensions

Dimension drawing of BC/BD-2X680DC5-B01 C
Dimension drawing
Dimensions as drawn
A 7750 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7300 mm
H 1200 mm
I 2310 mm
K 8250 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 7750 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.