Product code: BC/BD-2X680HB1-B01 C

Heat rejection i
468.00 kW
Air flow
201,381 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 201,381 m³/h
External surface 964.5 m²
Inner volume 155.8 dm³
Fin materialAluminium
Net weight 1,509 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.1 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X680HB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
467.999 kW Fluid flow 81.22 m³/h Pressure drop 35.2 kPa
Heat rejection · Low speed (Y)
377.102 kW Fluid flow 65.45 m³/h Pressure drop 23.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 258.99 not rated not rated not rated not rated not rated
40 468.00 262.01 not rated not rated not rated not rated
45 672.53 470.09 264.60 not rated not rated not rated
50 875.74 674.03 472.01 266.93 not rated not rated
55 1078.31 876.65 675.46 473.89 269.17 not rated
60 1280.57 1078.74 877.65 676.97 475.86 271.36

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 209.98 not rated not rated not rated not rated not rated
40 377.10 212.45 not rated not rated not rated not rated
45 540.00 378.73 214.53 not rated not rated not rated
50 701.64 541.08 380.08 216.39 not rated not rated
55 862.67 702.24 541.92 381.45 218.18 not rated
60 1023.38 862.84 702.64 542.97 382.97 219.96

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 467.999 81.22 35.2
Low speed (Y) 377.102 65.45 23.9

Dimensions

Dimension drawing of BC/BD-2X680HB1-B01 C
Dimension drawing
Dimensions as drawn
A 6850 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 6400 mm
H 1050 mm
I 2260 mm
K 7350 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 6850 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.