Skip to Content

Dry cooler BC/BD-691BD5-B04 C

Dry cooler BC/BD-691BD5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-691BD5-B04 C

Heat rejection i
468.46 kW
Air flow
142,886 m³/h
Fans
6 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 142,886 m³/h
External surface 1,523.5 m²
Inner volume 221.2 dm³
Fin materialAluminium
Net weight 1,356 kg
Fans
Quantity 6
Diameter 910 mm
Speed 840 rpm
Power 16,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 99.1 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-691BD5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
468.460 kW Fluid flow 81.30 m³/h Pressure drop 29.2 kPa
Heat rejection · Low speed (Y)
363.331 kW Fluid flow 63.06 m³/h Pressure drop 18.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 269.14 not rated not rated not rated not rated not rated
40 468.46 270.78 not rated not rated not rated not rated
45 662.40 468.70 272.19 not rated not rated not rated
50 854.63 661.52 469.01 273.57 not rated not rated
55 1046.00 852.65 660.89 469.60 275.02 not rated
60 1236.88 1042.96 851.18 660.80 470.51 276.57

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 211.00 not rated not rated not rated not rated not rated
40 363.33 212.32 not rated not rated not rated not rated
45 510.81 363.53 213.47 not rated not rated not rated
50 656.81 510.16 363.73 214.58 not rated not rated
55 802.06 655.35 509.70 364.18 215.75 not rated
60 946.91 799.85 654.24 509.64 364.96 217.07

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 468.460 81.30 29.2
Low speed (Y) 363.331 63.06 18.5

Dimensions

Dimension drawing of BC/BD-691BD5-B04 C
Dimension drawing
Dimensions as drawn
A 11050 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 10600 mm
H 1750 mm
I 1190 mm
K 11550 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 11550 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.