BC/BD-691BD5-B04 C
468.46 kW
Defrost: None
Product code: BC/BD-2x680CD1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 108,559 m³/h |
|---|---|
| External surface | 3,603.6 m² |
| Inner volume | 437.2 dm³ |
| Fin material | Aluminium |
| Net weight | 2,455 kg |
| Quantity | 12 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | B |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2x680CD1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 280.16 | not rated | not rated | not rated | not rated | not rated |
| 40 | 468.46 | 281.22 | not rated | not rated | not rated | not rated |
| 45 | 648.63 | 467.29 | 282.11 | not rated | not rated | not rated |
| 50 | 826.21 | 645.83 | 466.39 | 283.03 | not rated | not rated |
| 55 | 1002.59 | 821.93 | 643.59 | 465.91 | 284.09 | not rated |
| 60 | 1178.31 | 996.91 | 818.47 | 642.09 | 466.02 | 285.45 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 213.46 | not rated | not rated | not rated | not rated | not rated |
| 40 | 353.81 | 214.27 | not rated | not rated | not rated | not rated |
| 45 | 487.19 | 352.64 | 214.90 | not rated | not rated | not rated |
| 50 | 618.49 | 484.70 | 351.70 | 215.52 | not rated | not rated |
| 55 | 748.86 | 614.82 | 482.66 | 351.11 | 216.25 | not rated |
| 60 | 878.72 | 744.08 | 611.81 | 481.23 | 351.02 | 217.24 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 468.455 | 81.25 | 12.5 |
| Low speed (Y) | 353.805 | 61.40 | 7.5 |
| A | 11050 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 10600 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 11550 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 11550 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.