BC/BD-t-363AD5-B19 C
128.67 kW
Defrost: None
Product code: BC/BD-2x280AC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 32,575 m³/h |
|---|---|
| External surface | 658.9 m² |
| Inner volume | 86.7 dm³ |
| Fin material | Aluminium |
| Net weight | 655 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-2x280AC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 77.68 | not rated | not rated | not rated | not rated | not rated |
| 40 | 128.65 | 77.76 | not rated | not rated | not rated | not rated |
| 45 | 178.25 | 128.43 | 77.87 | not rated | not rated | not rated |
| 50 | 227.41 | 177.77 | 128.29 | 77.99 | not rated | not rated |
| 55 | 276.35 | 226.67 | 177.42 | 128.27 | 78.20 | not rated |
| 60 | 325.17 | 275.36 | 226.12 | 177.27 | 128.41 | 78.51 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 59.94 | not rated | not rated | not rated | not rated | not rated |
| 40 | 98.23 | 60.05 | not rated | not rated | not rated | not rated |
| 45 | 135.41 | 98.14 | 60.18 | not rated | not rated | not rated |
| 50 | 172.22 | 135.15 | 98.12 | 60.35 | not rated | not rated |
| 55 | 208.87 | 171.80 | 135.01 | 98.20 | 60.57 | not rated |
| 60 | 245.41 | 208.29 | 171.55 | 135.02 | 98.42 | 60.86 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 128.645 | 22.31 | 92.0 |
| Low speed (Y) | 98.234 | 17.04 | 57.1 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 3050 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3050 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.