BC/BD-680AD1-B01 C
338.03 kW
Defrost: None
Product code: BC/BD-2x380AD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 91,802 m³/h |
|---|---|
| External surface | 1,235.5 m² |
| Inner volume | 170.2 dm³ |
| Fin material | Aluminium |
| Net weight | 1,038 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.5 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2x380AD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 200.07 | not rated | not rated | not rated | not rated | not rated |
| 40 | 338.22 | 200.79 | not rated | not rated | not rated | not rated |
| 45 | 472.60 | 338.16 | 201.50 | not rated | not rated | not rated |
| 50 | 605.79 | 471.96 | 338.31 | 202.28 | not rated | not rated |
| 55 | 738.40 | 604.55 | 471.63 | 338.71 | 203.16 | not rated |
| 60 | 870.68 | 736.59 | 603.79 | 471.75 | 339.46 | 204.26 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 155.38 | not rated | not rated | not rated | not rated | not rated |
| 40 | 259.56 | 155.94 | not rated | not rated | not rated | not rated |
| 45 | 360.65 | 259.52 | 156.46 | not rated | not rated | not rated |
| 50 | 460.68 | 360.11 | 259.61 | 157.00 | not rated | not rated |
| 55 | 560.22 | 459.70 | 359.84 | 259.89 | 157.72 | not rated |
| 60 | 659.49 | 558.81 | 459.09 | 359.89 | 260.49 | 158.60 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 338.218 | 58.71 | 74.4 |
| Low speed (Y) | 259.564 | 45.02 | 46.4 |
| A | 3950 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3700 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 4250 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4250 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.