Skip to Content

Dry cooler BC/BD-680AD1-B01 C

Dry cooler BC/BD-680AD1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-680AD1-B01 C

Heat rejection i
338.03 kW
Air flow
91,802 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 91,802 m³/h
External surface 1,235.5 m²
Inner volume 150.7 dm³
Fin materialAluminium
Net weight 1,098 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 90.5 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-680AD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
338.025 kW Fluid flow 58.66 m³/h Pressure drop 70.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
259.439 kW Fluid flow 45.00 m³/h Pressure drop 44.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 199.87 not rated not rated not rated not rated not rated
40 338.03 200.61 not rated not rated not rated not rated
45 472.43 337.99 201.32 not rated not rated not rated
50 605.63 471.80 338.14 202.11 not rated not rated
55 738.24 604.40 471.47 338.56 203.00 not rated
60 870.52 736.44 603.64 471.59 339.31 204.10

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 155.24 not rated not rated not rated not rated not rated
40 259.44 155.79 not rated not rated not rated not rated
45 360.53 259.40 156.35 not rated not rated not rated
50 460.57 360.00 259.50 156.88 not rated not rated
55 560.11 459.59 359.74 259.78 157.60 not rated
60 659.39 558.71 458.99 359.79 260.38 158.49

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 338.025 58.66 70.9
Low speed (Y) 259.439 45.00 44.2

Dimensions

Dimension drawing of BC/BD-680AD1-B01 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 7300 mm
H 1200 mm
I 1190 mm
K 7850 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7850 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.