BC/BD-680AD1-B01 C
338.03 kW
Defrost: None
Product code: BC/BD-t-2X563AD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 74,164 m³/h |
|---|---|
| External surface | 1,148.2 m² |
| Inner volume | 173.4 dm³ |
| Fin material | Aluminium |
| Net weight | 908 kg |
| Quantity | 10 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 6,000 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.1 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-t-2X563AD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 206.93 | not rated | not rated | not rated | not rated | not rated |
| 40 | 337.74 | 207.11 | not rated | not rated | not rated | not rated |
| 45 | 463.27 | 336.53 | 207.31 | not rated | not rated | not rated |
| 50 | 587.09 | 460.96 | 335.60 | 207.62 | not rated | not rated |
| 55 | 710.13 | 583.79 | 459.16 | 335.06 | 208.13 | not rated |
| 60 | 832.75 | 705.88 | 581.17 | 457.97 | 335.04 | 208.96 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 337.736 | 58.58 | 30.9 |
| A | 4950 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4600 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 5300 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 4950 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.