Skip to Content

Dry cooler BC/BD-2x380OC1-B01 C

Dry cooler BC/BD-2x380OC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x380OC1-B01 C

Heat rejection i
469.24 kW
Air flow
120,113 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 120,113 m³/h
External surface 1,875.7 m²
Inner volume 359.9 dm³
Fin materialAluminium
Net weight 1,491 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x380OC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
469.239 kW Fluid flow 81.37 m³/h Pressure drop 67.1 kPa
Heat rejection · Low speed (Y)
358.633 kW Fluid flow 62.19 m³/h Pressure drop 41.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 281.70 not rated not rated not rated not rated not rated
40 469.24 281.61 not rated not rated not rated not rated
45 651.74 467.64 281.56 not rated not rated not rated
50 832.50 648.72 466.29 281.64 not rated not rated
55 1012.46 828.13 646.18 465.32 281.78 not rated
60 1191.98 1006.78 824.45 644.27 464.75 282.29

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 217.53 not rated not rated not rated not rated not rated
40 358.63 217.37 not rated not rated not rated not rated
45 495.54 357.21 217.23 not rated not rated not rated
50 631.06 493.01 356.03 217.23 not rated not rated
55 765.92 627.45 490.89 355.21 217.41 not rated
60 900.43 761.28 624.44 489.32 354.82 217.86

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 469.239 81.37 67.1
Low speed (Y) 358.633 62.19 41.4

Dimensions

Dimension drawing of BC/BD-2x380OC1-B01 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7300 mm
H 2400 mm
I 2310 mm
K 7850 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7850 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.