Product code: BC/BD-2x491GD1-B04 C

Heat rejection i
772.06 kW
Air flow
206,507 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 206,507 m³/h
External surface 3,294.7 m²
Inner volume 433.1 dm³
Fin materialAluminium
Net weight 2,134 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 99.6 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2x491GD1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
772.059 kW Fluid flow 133.88 m³/h Pressure drop 22.6 kPa
Heat rejection · Low speed (Y)
594.864 kW Fluid flow 103.16 m³/h Pressure drop 14.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 447.58 not rated not rated not rated not rated not rated
40 772.06 449.89 not rated not rated not rated not rated
45 1085.73 771.25 451.88 not rated not rated not rated
50 1395.77 1082.33 770.57 453.74 not rated not rated
55 1704.06 1389.93 1079.49 770.36 455.63 not rated
60 2011.38 1695.92 1385.08 1077.54 770.79 457.87

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 348.72 not rated not rated not rated not rated not rated
40 594.86 350.56 not rated not rated not rated not rated
45 831.48 594.08 352.13 not rated not rated not rated
50 1064.91 828.69 593.52 353.63 not rated not rated
55 1296.88 1060.30 826.47 593.40 355.24 not rated
60 1528.01 1290.52 1056.57 825.05 593.87 357.13

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 772.059 133.88 22.6
Low speed (Y) 594.864 103.16 14.1

Dimensions

Dimension drawing of BC/BD-2x491GD1-B04 C
Dimension drawing
Dimensions as drawn
A 10150 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 9700 mm
H 2400 mm
I 2310 mm
K 10650 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 10650 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.