BC/BD-2X880AC5-B01 C
769.05 kW
Defrost: None
Product code: BC/BD-2x591BD5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 238,144 m³/h |
|---|---|
| External surface | 2,539.1 m² |
| Inner volume | 403.0 dm³ |
| Fin material | Aluminium |
| Net weight | 2,076 kg |
| Quantity | 10 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 28,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 101.1 dB(A) |
| Energy class | E |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BC/BD-2x591BD5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 435.25 | not rated | not rated | not rated | not rated | not rated |
| 40 | 768.97 | 438.94 | not rated | not rated | not rated | not rated |
| 45 | 1092.85 | 770.08 | 442.14 | not rated | not rated | not rated |
| 50 | 1413.60 | 1091.98 | 771.19 | 445.17 | not rated | not rated |
| 55 | 1732.91 | 1410.86 | 1091.43 | 772.65 | 448.10 | not rated |
| 60 | 2051.35 | 1728.39 | 1408.80 | 1091.72 | 774.64 | 451.17 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 341.35 | not rated | not rated | not rated | not rated | not rated |
| 40 | 596.95 | 344.42 | not rated | not rated | not rated | not rated |
| 45 | 843.46 | 597.86 | 347.07 | not rated | not rated | not rated |
| 50 | 1087.19 | 842.82 | 598.74 | 349.49 | not rated | not rated |
| 55 | 1329.57 | 1085.14 | 842.42 | 599.78 | 351.91 | not rated |
| 60 | 1571.20 | 1326.21 | 1083.60 | 842.65 | 601.43 | 354.50 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 768.974 | 133.47 | 21.1 |
| Low speed (Y) | 596.953 | 103.61 | 13.3 |
| A | 9300 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 8850 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 9800 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 9800 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.