Skip to Content

Dry cooler BC/BD-2x791FB5-B04 C

Dry cooler BC/BD-2x791FB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x791FB5-B04 C

Heat rejection i
771.19 kW
Air flow
326,828 m³/h
Fans
14 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 326,828 m³/h
External surface 1,622.9 m²
Inner volume 419.5 dm³
Fin materialAluminium
Net weight 2,227 kg
Fans
Quantity 14
Diameter 910 mm
Speed 840 rpm
Power 39,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 71.0 dB(A)
Sound power 103.3 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2x791FB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
771.193 kW Fluid flow 133.84 m³/h Pressure drop 20.4 kPa
Heat rejection · Low speed (Y)
not rated

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 422.63 not rated not rated not rated not rated not rated
40 771.19 427.72 not rated not rated not rated not rated
45 1112.61 774.49 432.12 not rated not rated not rated
50 1451.87 1114.58 777.53 436.10 not rated not rated
55 1790.14 1452.53 1116.54 780.59 439.85 not rated
60 2127.77 1789.61 1453.50 1118.78 783.76 443.56

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 not rated not rated not rated not rated not rated not rated
40 not rated not rated not rated not rated not rated not rated
45 not rated not rated not rated not rated not rated not rated
50 not rated not rated not rated not rated not rated not rated
55 not rated not rated not rated not rated 353.87 not rated
60 not rated not rated not rated not rated 625.06 357.00

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 771.193 133.84 20.4
Low speed (Y) — — —

Dimensions

Dimension drawing of BC/BD-2x791FB5-B04 C
Dimension drawing
Dimensions as drawn
A 10350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 9900 mm
H 1400 mm
I 2310 mm
K 10850 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 10850 mm
Width 2360 mm
Height 1450 mm

Downloads