Skip to Content

Dry cooler BC/BD-2x691DB5-B04 C

Dry cooler BC/BD-2x691DB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x691DB5-B04 C

Heat rejection i
759.96 kW
Air flow
302,501 m³/h
Fans
12 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 302,501 m³/h
External surface 1,738.8 m²
Inner volume 442.9 dm³
Fin materialAluminium
Net weight 2,161 kg
Fans
Quantity 12
Diameter 910 mm
Speed 840 rpm
Power 33,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 69.0 dB(A)
Sound power 101.9 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2x691DB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
759.964 kW Fluid flow 131.91 m³/h Pressure drop 20.8 kPa
Heat rejection · Low speed (Y)
608.661 kW Fluid flow 105.63 m³/h Pressure drop 13.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 420.76 not rated not rated not rated not rated not rated
40 759.96 425.01 not rated not rated not rated not rated
45 1091.86 762.27 428.70 not rated not rated not rated
50 1421.47 1092.58 764.40 432.08 not rated not rated
55 1750.09 1420.78 1093.42 766.54 435.21 not rated
60 2078.06 1747.95 1420.41 1094.59 768.90 438.33

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 339.66 not rated not rated not rated not rated not rated
40 608.66 343.18 not rated not rated not rated not rated
45 870.87 610.49 346.24 not rated not rated not rated
50 1130.85 871.40 612.26 349.03 not rated not rated
55 1389.89 1130.21 872.10 614.08 351.75 not rated
60 1648.32 1388.14 1130.03 873.18 616.15 354.37

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 759.964 131.91 20.8
Low speed (Y) 608.661 105.63 13.9

Dimensions

Dimension drawing of BC/BD-2x691DB5-B04 C
Dimension drawing
Dimensions as drawn
A 11050 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 10600 mm
H 1750 mm
I 2310 mm
K 11550 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 11550 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.