BC/BD-380AB5-B01 C
126.62 kW
Defrost: None
Product code: BC/BD-380NC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 31,057 m³/h |
|---|---|
| External surface | 835.4 m² |
| Inner volume | 111.2 dm³ |
| Fin material | Aluminium |
| Net weight | 764 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 37.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | B |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-380NC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 77.00 | not rated | not rated | not rated | not rated | not rated |
| 40 | 126.50 | 76.83 | not rated | not rated | not rated | not rated |
| 45 | 174.64 | 125.88 | 76.69 | not rated | not rated | not rated |
| 50 | 222.34 | 173.62 | 125.35 | 76.58 | not rated | not rated |
| 55 | 269.83 | 220.92 | 172.74 | 124.94 | 76.55 | not rated |
| 60 | 317.22 | 268.03 | 219.71 | 172.05 | 124.69 | 76.61 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 61.15 | not rated | not rated | not rated | not rated | not rated |
| 40 | 99.60 | 61.02 | not rated | not rated | not rated | not rated |
| 45 | 136.93 | 99.11 | 60.90 | not rated | not rated | not rated |
| 50 | 173.90 | 136.12 | 98.69 | 60.82 | not rated | not rated |
| 55 | 210.70 | 172.79 | 135.44 | 98.37 | 60.80 | not rated |
| 60 | 247.42 | 209.29 | 171.84 | 134.90 | 98.19 | 60.87 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 126.497 | 21.94 | 58.2 |
| Low speed (Y) | 99.600 | 17.27 | 38.0 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7300 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 7850 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 7850 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.