BC/BD-2x580HB5-B03 C
234.79 kW
Defrost: None
Product code: BC/BD-380OC1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 60,057 m³/h |
|---|---|
| External surface | 937.8 m² |
| Inner volume | 172.2 dm³ |
| Fin material | Aluminium |
| Net weight | 821 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-380OC1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 140.85 | not rated | not rated | not rated | not rated | not rated |
| 40 | 234.62 | 140.81 | not rated | not rated | not rated | not rated |
| 45 | 325.87 | 233.82 | 140.78 | not rated | not rated | not rated |
| 50 | 416.25 | 324.36 | 233.14 | 140.82 | not rated | not rated |
| 55 | 506.23 | 414.07 | 323.09 | 232.66 | 140.89 | not rated |
| 60 | 595.99 | 503.39 | 412.23 | 322.14 | 232.38 | 141.15 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 108.76 | not rated | not rated | not rated | not rated | not rated |
| 40 | 179.32 | 108.68 | not rated | not rated | not rated | not rated |
| 45 | 247.77 | 178.61 | 108.62 | not rated | not rated | not rated |
| 50 | 315.53 | 246.50 | 178.02 | 108.62 | not rated | not rated |
| 55 | 382.96 | 313.73 | 245.44 | 177.60 | 108.70 | not rated |
| 60 | 450.21 | 380.64 | 312.22 | 244.66 | 177.41 | 108.93 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 234.620 | 40.69 | 63.0 |
| Low speed (Y) | 179.317 | 31.10 | 39.0 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7300 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 7850 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 7850 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.